DB-PX5 - PowerVisa 440® / PowerGuide® 4400 / PowerXplorer® PX5 Op. Skills
© 2006-2010 by PowerCET Corporation. All rights reserved. (100616)
44
©2006-2008 PowerCET Corporation. All rights reserved.
87
The PX5's high frequency
card allows it to capture high-
frequency transients
(>2µSec)
If applicable, Press: Group A
B C to simplify setup
Press the limit field and enter
the limit.
Press: Enable
Press Amps to toggle
between volts and amps
Press the other tabs to set
other channels
Press: Next to continue
•* only available on
PowerXplorer PX5
Wizard Setup: PX5 Transient Limits-Hi Frequency Detectors*
©2006-2008 PowerCET Corporation. All rights reserved.
88
Press limit field under Threshold to
change limit
If the wave samples differ by
more than the threshold
tolerance for a time exceeding
the Duration or window percent
of power frequency cycle, a
waveshape fault is registered.
Useful for capturing low-mid
frequency transients
Press limit field under Duration to
change limit
Press: Enable
Press Amps to toggle between
volts and amps
Press the other tabs to set other
channels
Press: Next to continue
Wizard Setup: Transient Limits-Waveshape Fault Detection