•To record data,
press: Continue
and set limits...
•then Press: Next
•(Cancel discards
changes and
returns to Start
menu)
Wizard Setup: Mode of Operation
©2006-2008 PowerCET Corporation. All rights reserved.
82
•Gives you a choice of
templates for parameter
thresholds setup:
• Standard Power Quality,
Demand, Energy (default)
optimizes the instrument to
collect data for
troubleshooting using
standard power quality
parameters, with numerous
trigger conditions set (used
by smart start/autoconfig)
• Current Inrush is ideal for
recording motor start-up and
inrush conditions. It triggers
on change in current with
longer cycle-by-cycle
waveform capture than
Standard Power Quality
• Fault Recorder is similar to
Inrush but with a voltage
trigger
Wizard Setup: Monitoring Mode