CH 2/ Voltage Measurement Cables and Current Probe Connections
Example:
Neutral to
ground
connection
The following figure shows a voltage connection using channel D as a differential input
for measuring neutral to ground voltage. Connections are identical for split phase and
wye configurations. One probe connects the source neutral line to the D+ input.
Another probe connects the ground to the D- input.
PX5-13.vsd
Vedere la pagina 36